Valve Cv calculator (flow coefficient)
By a practising automation / electrical engineer with more than ten years · Updated 2026-11-22
Liquid, incompressible: Cv = Q × √(SG / ΔP) with Q in USGPM and ΔP in psi. Example: 100 USGPM, SG 1, 25 psi → Cv 20. Sizing aid only — not a control-valve datasheet, not AutoCAD/EPLAN, and not ISA/IEC certified.
Cv 20
Liquid valve flow coefficient
For incompressible liquid, Cv = Q × √(SG / ΔP) with Q in US gallons per minute and ΔP in psi. Water (SG = 1) at 100 USGPM and 25 psi drop gives Cv = 20. SI inputs (m³/h and bar) are converted to that basis before the formula.
ΔP must not be zero. Empty or non-numeric fields are rejected. The result is a sizing number for a first pass, not a manufacturer’s published Cv curve.
What this calculator is not
It is not a control-valve datasheet, not compressible-gas sizing, not flashing or two-phase, and not ISA/IEC certified. It does not pick a body, trim, or actuator.
SchematicForge issues loop diagrams from an IO list. A valve tag on that list still needs the Cv you (or the vendor) calculated elsewhere. Not AutoCAD, not EPLAN.
Frequently asked questions
What units does Cv use?
USGPM of water-equivalent flow at 1 psi drop. SI m³/h and bar are converted internally. 100 USGPM, SG 1, 25 psi → Cv 20.
Does this size gas or steam?
No. Liquid, incompressible only. Gas, steam, flashing, and two-phase need a different equation and vendor data.
Is this a certified valve calculation?
No. It is a screening Cv. Manufacturer software and the project specification remain the authority.