Orifice plate flow calculator
By a practising automation / electrical engineer with more than ten years · Updated 2026-11-22
Screening estimate with default β = 0.5 and C = 0.61. Not a meter run, not AGA-3, not custody transfer, and not ISA/IEC certified.
- 19.916 m³/h (87.685 USGPM)
- Orifice bore 50 mm at β 0.5
Screening orifice flow
Volumetric flow is estimated as Q = C / √(1 − β⁴) × (π/4) d² × √(2 ΔP / ρ) with C = 0.61 and default β = 0.5. Pipe D is inside diameter. ΔP must not be zero.
The figure is a screening estimate for a first look at bore and drop. It is not an ISO 5167 / AGA-3 meter-run calculation and not custody transfer.
What this calculator is not
It does not apply expansibility, tap location, drain holes, or upstream/downstream pipe runs. Density is a user input, not a PVT flash.
An orifice on an IO list still needs a vendor meter run if it is a fiscal or allocation meter. SchematicForge draws the loop from the list; it does not size the plate. Not ISA/IEC certified.
Frequently asked questions
Is this an AGA-3 or ISO 5167 calculation?
No. C is fixed at 0.61 and β defaults to 0.5. Use a meter-run package for custody or allocation.
What happens if ΔP is zero?
The tool rejects it. Flow is undefined at zero differential.
Will SchematicForge print the bore on a loop sheet?
No. Loop sheets come from the IO list. This page is a screening calculator only.