Free Cable Schedule Excel template
By a practising automation / electrical engineer with more than ten years · Updated 2026-11-22
Cable schedule Excel: one row per field cable with Cable ID, from, to, cores, and loop tag. Import an IO list to generate the project schedule.
Sheet: Cable Schedule. Includes an Instructions tab and example rows.
Download XLSXColumns
| Column | Required | Note |
|---|---|---|
| Cable ID | Yes | Unique field-cable identifier |
| Cable Type | No | e.g. Instrument |
| Core Count | No | Declared cores, not a sum of signals |
| From Location | No | Usually the JB |
| To Location | No | Usually marshalling or the device |
| Loop Tag | No | Loop this cable serves |
| Length (m) | No | Optional |
| Route | No | Tray or route note |
| Notes | No | Free text |
Example rows
| Cable ID | Cable Type | Core Count | From Location | To Location | Loop Tag | Length (m) | Route |
|---|---|---|---|---|---|---|---|
| C-F-1001 | Instrument | 2 | JB-01 | PT-1001 | PT-1001 | 120 | Tray T1 |
| C-F-2001 | Instrument | 2 | JB-02 | FT-2001 | FT-2001 | 85 | Tray T2 |
First eight columns shown. Download the XLSX for the full sheet.
One row per field cable
A cable schedule is indexed by cable, not by signal. If Cable C-F-1001 carries a shared pair for several signals, it is still one row. Collapsing signals to cables is the core of cable scheduling and the most common mistake in a hand-built sheet.
Cable ID is the key. From and To name the two ends — usually a junction box and the marshalling cabinet. Loop Tag records which loop the cable serves, which links it back to the loop diagrams.
Cores are declared, not summed
Core Count is the physical pair or multicore declared for that cable, such as 2 for a single instrument pair or 12 for a multicore. It is never the number of signals you happen to list on it.
Length, Route, and Notes are free fields for tray references and pulling notes. They travel with the schedule and do not affect the drawings.
From schedule to loop sheet
Because the schedule is built from the same IO list as the diagrams, each cable appears on the loop sheet that uses it. The property that matters to a reviewer is that the schedule and the drawings cannot disagree.
Use the blank template for a manual schedule, the free cable schedule tool for up to ten cables, and the generated project schedule once you upload the vendor IO list.
Importing this workbook works like a vendor IO list — upload it in the IO list checker or on the home page, review the mapping, and create loops.