Range low / range high
By a practising automation / electrical engineer with more than ten years · Updated 2026-11-22
The engineering-unit values mapped to the bottom and top of a signal span, e.g. 0–10 bar.
Range low is the process value at the bottom of the electrical span (usually 4 mA on a 4–20 mA transmitter). Range high is the value at the top of span (usually 20 mA). Units sit in a separate column: barg, °C, m3/h.
On an IO list, keep Range Low and Range High numeric. 0 and 10 with Units barg means 0–10 barg. SchematicForge prints those three fields next to the transmitter on the loop diagram. They do not change the wiring.
Do not put 4 and 20 in the range columns unless the process units really are milliamps. 4–20 mA is the signal type, not the engineering range.
A common commissioning fault is correct wiring with a swapped range, which reads plausibly but is wrong. Checking range low, range high, and units against the instrument datasheet is part of the loop check, not an administrative detail.
SchematicForge uses this term in generated loop diagrams, the Loop Register, and termination lists.