4–20 mA scaling calculator

By a practising automation / electrical engineer with more than ten years · Updated 2026-11-22

Linear scale: PV = PVmin + (mA − 4) / 16 × (PVmax − PVmin). Default 0–100 at 12 mA → 50. Optional 250 Ω voltage (1–5 V). This is a scaling calculator, not a wiring diagram, not a generated loop sheet, and not ISA/IEC certified.

  • PV 50 at 12 mA (50% of span)
  • 250 Ω drop: 3 V

The linear 4–20 mA scale

A live-zero current loop maps 4 mA to PV min and 20 mA to PV max. The process value is PV = PVmin + (mA − 4) / 16 × (PVmax − PVmin). On a 0–100 range, 12 mA is 50 — half span, the usual live-zero check.

The reverse is mA = 4 + 16 × (PV − PVmin) / (PVmax − PVmin). PV max must differ from PV min. Empty or non-numeric fields are rejected rather than guessed.

250 Ω and what this is not

A 250 Ω precision resistor turns 4–20 mA into 1–5 V. The optional volts reading is mA × 0.25. It is a check figure, not a loop-powered supply calculation.

This page is a scaling calculator. Conductor roles for 2-wire, 3-wire, 4-wire, RTD, and thermocouple live on the wiring reference. SchematicForge does not generate a loop sheet from these numbers; upload an IO list for drawings. Not ISA/IEC certified.

Frequently asked questions

Why is 12 mA equal to 50 on a 0–100 range?

12 mA is halfway between 4 and 20, so it is 50 percent of span. PV = 0 + (12 − 4) / 16 × 100 = 50.

Is this a wiring diagram?

No. Use the 4–20 mA wiring reference for 2-wire, 3-wire, 4-wire, RTD, and thermocouple conductors. This page only scales current to process value.

Will SchematicForge print this scale on a loop sheet?

Loop sheets come from an IO list, not from this calculator. Range low and range high on the list are what appear on the drawing.