Pt100 RTD calculator
By a practising automation / electrical engineer with more than ten years · Updated 2026-11-22
IEC 60751 Pt100, α = 0.00385. 0 °C = 100 Ω, 100 °C ≈ 138.51 Ω. Range −200 to 850 °C. Not a calibration certificate, not a generated loop sheet, and not ISA/IEC certified.
100 °C = 138.51 Ω
IEC 60751 Pt100
A Pt100 is 100 Ω at 0 °C with α = 0.00385. Callendar–Van Dusen coefficients A = 3.9083×10⁻³, B = −5.775×10⁻⁷, and C = −4.183×10⁻¹² below 0 °C give 100 °C ≈ 138.51 Ω. The range is −200 to 850 °C.
Empty or non-numeric input is rejected. Values outside the IEC range are rejected rather than extrapolated.
Wiring versus resistance
This page converts temperature and resistance. 2-wire, 3-wire, and 4-wire lead compensation is a wiring problem — see the 4–20 mA wiring reference RTD panel. A head-mounted transmitter turns the RTD into 4–20 mA; then use the scaling calculator.
Not a calibration certificate, not a generated loop sheet, and not ISA/IEC certified. SchematicForge uses the tag and range you put on the IO list.
Frequently asked questions
What is 100 °C on a Pt100?
About 138.51 Ω on IEC 60751 α = 0.00385. 0 °C is 100 Ω.
Does this include lead-wire compensation?
No. Compensation is 3-wire or 4-wire at the card, or inside a head transmitter. This tool is resistance versus temperature only.
Is this a calibration certificate?
No. It is an IEC 60751 conversion. A certificate comes from a lab on the installed sensor.