Free Termination List Excel template
By a practising automation / electrical engineer with more than ten years · Updated 2026-11-22
Termination list Excel: JB and marshalling terminal pairs, wire numbers, and destinations per signal. The tabular half of a termination diagram.
Sheet: Termination List. Includes an Instructions tab and example rows.
Download XLSXColumns
| Column | Required | Note |
|---|---|---|
| Loop Tag | Yes | Instrument tag |
| Signal | No | AI, AO, DI, DO |
| JB Name | No | Field junction box |
| JB Terminal From | No | First JB terminal |
| JB Terminal To | No | Second JB terminal |
| Marshalling Cabinet | No | Cabinet name |
| Strip | No | Marshalling strip |
| Terminal From | No | First marsh terminal |
| Terminal To | No | Second marsh terminal |
| Wire Number | No | Matches the signal wire number |
| Notes | No | Free text |
Example rows
| Loop Tag | Signal | JB Name | JB Terminal From | JB Terminal To | Marshalling Cabinet | Strip | Terminal From |
|---|---|---|---|---|---|---|---|
| PT-1001 | AI | JB-01 | 1 | 2 | MC-01 | S-1 | 11 |
| FT-2001 | AI | JB-02 | 1 | 2 | MC-01 | S-2 | 21 |
First eight columns shown. Download the XLSX for the full sheet.
What a termination list contains
A termination list is the connection book for commissioning. One row per signal records the loop tag, signal type, junction box with its two terminals, the marshalling cabinet and strip with their two terminals, and the wire number.
It is the tabular half of a termination diagram: the diagram draws the same connections on the loop sheet, and the list gives the electrician a sortable view.
JB terminals vs marshalling terminals
Field terminals live in the junction box, where the instrument cable lands. Marshalling terminals live in the control-room cabinet, where the field cable is jumpered to the I/O-card cable. Both ends appear on the same row so a loop can be traced point to point.
Worked example: PT-1001, analog input, lands on JB-01 terminals 1–2 and on marshalling strip S-1 terminals 11–12 with wire number 1-11.
Wire numbers
The wire number is the printed identifier that ties the physical conductor to the drawing. It is stored per signal, so it appears identically on the termination list, the loop sheet, and the ferrule labels.
Uniqueness is checked where the number is printed, inside the loop, which is the same rule the generated drawings follow.
Importing this workbook works like a vendor IO list — upload it in the IO list checker or on the home page, review the mapping, and create loops.