Digital output (DO)
By a practising automation / electrical engineer with more than ten years · Updated 2026-11-22
A two-state output used to energise a solenoid, lamp, or motor starter.
A digital output energises a two-state field device: a solenoid valve, a lamp, a relay, or a motor starter coil. It is a switched 24 VDC or relay contact from the controller.
Like a digital input, it is one signal within a loop and carries its own terminals, channel, and tag entry in the PLC tag list.
Digital outputs usually drive something that can cause movement, so the drawing has to make the energised state unambiguous. A solenoid shown energised-to-open behaves the opposite way when the coil fails, and that distinction matters for the loop check and for the safe state documented for the loop.
Confirm the de-energised state for every digital output at commissioning, since that is the state the plant returns to on a power loss and the one that most affects safety.
SchematicForge uses this term in generated loop diagrams, the Loop Register, and termination lists.