Digital input (DI)
By a practising automation / electrical engineer with more than ten years · Updated 2026-11-22
A two-state input carrying a status, such as a switch or alarm contact.
A digital input carries a two-state field status into the controller: a valve limit switch, a pressure switch, a motor running contact, or an alarm. It is read as a dry contact or a 24 VDC level.
On the loop sheet a digital input is drawn as a contact pair on the same loop as the device it monitors, with its own junction-box terminals and channel.
Digital inputs are typically dry contacts or a 24 VDC level, and the drawing should say which. A wet contact fed from a different source than the card supply will not read correctly, and a shared common across several inputs can tie loops together in ways the sheet must show.
Note whether each digital input is normally-open or normally-closed at the field, because the safe reading on a signal failure depends on it and the drawing should not leave it implied.