Analog output (AO)
By a practising automation / electrical engineer with more than ten years · Updated 2026-11-22
A continuous output signal a controller uses to position a device such as a control valve.
An analog output drives a continuously positioned device, most often a control valve or a variable-speed drive. It is a 4–20 mA signal from the controller to the field, the mirror of an analog input.
A control valve is typically one loop with an analog output plus discrete limit-switch inputs, so several signals share the same tag.
Analog outputs need a fail-safe direction agreed before commissioning. A control valve should drive open, closed, or hold when the signal drops, and the actuator setting encodes that choice. The loop sheet shows the output and the device; the fail-safe position belongs in the loop notes so it is checkable in the field.
Where a valve has a positioner, the loop carries the AO to the positioner and the position feedback as an AI; keep both on the same tag so the loop test covers the whole assembly.
SchematicForge uses this term in generated loop diagrams, the Loop Register, and termination lists.