Loop
By a practising automation / electrical engineer with more than ten years · Updated 2026-11-22
The complete instrument circuit from field device to controller: sensors, transmitters, cables, terminations, and the controller channel.
On an IO list, one tag is one loop. Two rows with the same tag (for example a valve AO plus two limit-switch DIs) are still one loop with three signals.
SchematicForge stores that as a Loop Register row plus one Signals row per I/O. The loop diagram, cable schedule, and termination list all key off the same tag.
A loop is the unit of testing as well as of drawing. Loop 1001 is checked, signed, and handed over as one item, which is why multi-signal devices stay under one tag rather than becoming separate loops. Splitting them would multiply the test records without changing the field wiring.
A loop is closed only when the controller reads the field device and drives the final element; an open loop with no output is a monitoring point, and should be labelled as one.
SchematicForge uses this term in generated loop diagrams, the Loop Register, and termination lists.