Free Alarm Register Excel template

By a practising automation / electrical engineer with more than ten years · Updated 2026-11-22

ISA-18.2 Alarm Register Excel: tag, type, setpoint, priority, plus empty workshop columns. Not a live DCS summary.

Sheet: Alarm Register. Includes an Instructions tab and example rows.

Download XLSX

Columns

ColumnRequiredNote
TagYesConfigured alarm identifier, e.g. PAH-1001
Alarm typeYesH, L, HH, LL, deviation, or house code
SetpointNoDocumented trip, not a live PV
UnitsNoe.g. bar
Existing priorityNoWhat the DCS already uses
DescriptionNoService text for the room
P&IDNoDrawing reference
AreaNoPlant area or console
ConsequenceNoWorkshop field — leave blank until signed
Operator response timeNoWorkshop field
Recommended priorityNoWorkshop recommendation, not an approval
Operator actionNoWhat the board does
Possible causeNoWorkshop field
ClassificationNoe.g. process / safety / suppress

Example rows

TagAlarm typeSetpointUnitsExisting priorityDescriptionP&IDArea
PAH-1001H12.5bar3V-1001 high pressure10-P-001Unit 10
FAL-2001L12m3/h—Cooling water low flow10-P-002Unit 10

First eight columns shown. Download the XLSX for the full sheet.

What the Alarm Register template is for

The Alarm Register is the master list a rationalization workshop works from: one row per configured alarm, not a live DCS summary and not an event log. Tag and Alarm type identify the row. Setpoint, units, existing priority, description, P&ID, and area tell the room which vessel they are talking about.

Consequence, operator response time, recommended priority, operator action, possible cause, and classification stay empty until the workshop fills them. Those columns are the ISA-18.2 rationalization record on the same keys.

How it differs from a DCS alarm log

A log is timed events. This sheet is the configured list. Drop either file on /alarm for chatter and flood counts; the paid pack is still built from unique configured alarms.

The blank Excel here is ungated. The 25-tag watermarked sample from the health check is a filled slice. The full workbook is the alarm-count pack.

What this template is not

It is not PAS, TiPS, or a live console. It is not an ISA-18.2 certificate. Priority in the Recommended priority column is a workshop recommendation until an engineer signs it. Loop diagrams stay on the IO-list product.

Importing this workbook works like a vendor IO list — upload it in the IO list checker or on the home page, review the mapping, and create loops.