How instrument wire numbers are assigned

By a practising automation / electrical engineer with more than ten years · Updated 2026-11-22

Wire numbers must be unique where they are printed. SchematicForge stores them per signal and draws them on the loop sheet from the same loop data.

Unique in the loop versus unique in the project

A ferrule that repeats PT-1001-1 on two loops will be printed twice. Commissioning wants a number that is unique on the job. Many shops still number per loop and accept the prefix as the discriminator.

SchematicForge validation rule V18 flags a duplicate wire number inside one loop. It does not yet reject the same number used on two tags.

Where the number is stored

Each signal has a wire_numbers list, one entry per core. If the list is empty, the drawing engine generates {tag}-{seq}-{core}. Overrides you type in the Loop Register are kept.

Those numbers print beside the wire on the loop sheet and appear on the termination list. Paid packs also download a from-to conductor CSV and a ferrule CSV from the same numbers.

Worked example

PT-1001 signal 1, two cores, no override: PT-1001-1-1 and PT-1001-1-2. A typical analog pair on JB-01 terminals 1–2. If you set wire_numbers to 1-11 and 1-12, the sheet and the termination list both show 1-11 / 1-12.