The cabinet in the control room where field cables terminate and are jumpered to controller I/O cables.

A marshalling cabinet is the interface between field wiring and the control system. Field cables land on one side and I/O-card tails on the other, so a loop can be re-terminated or a barrier swapped without disturbing the field multicore.

It differs from a junction box: a JB is in the field, close to the instruments it serves, while the marshalling cabinet is in the control room or rack room near the controller.

On the IO list the marshalling columns (cabinet, strip, terminal) route each signal through the cabinet. SchematicForge prints those terminations on the loop sheet and the termination list so the field and the cabinet agree.

Keep cabinet, strip, and terminal on the IO list so the cabinet drawing and the loop sheets agree. A signal re-terminated in the cabinet without a drawing update is a common cause of commissioning delay, because the field and the control room then work from different references.

SchematicForge uses this term in generated loop diagrams, the Loop Register, and termination lists.